|
Of Loadlines Power Output and Distortion - Part 5
Of Loadlines, Power Output and Distortion - Part 5 - The
Pentode
Purpose
In the preceding parts of this series, we concentrated on loadlines and triode
operation. In this article we will explore establishing a loadline on a pentode
vacuum tube (valve), determine the power available from this loadline, and
the distortion predicted from this loadline. This will allow the reader a
step by step way to calculate the parameters for his design. I have again
chosen to "invent" a tube for illustrative purposes. My pentode has the following
parameters:
Establishing a Load Line: (very similar to a triode for S.E.
applications)
-
Get the tube characteristics for your design (shown above for my example).
If not already on the characteristics, plot the maximum
power dissipation curve (voltage * current = spec'd power).
-
Select a reasonable quiescent operating point for your design. Often this
is described in the manufacturers typical operation. For instance, a reasonable
starting point for my example would be 300 volts and 83 mA. Whatever you
pick MUST BE within the tube's ratings. Put a dot on the tube characteristics
at this point.
-
Now start drawing a potential load line. This is a straight line whose "slope"
is the primary "impedance" of the transformer. How do you do this? Pick a
point somewhere about DOUBLE the quiescent voltage and zero plate (anode)
current. Draw a line (called "loadline" in the curve below) thru these 2
points extending to the 0 plate volt axis. Did your loadline go above the
max power curve you drew? Not good. Go back, pick a different zero current
point. Is the voltage at no current more than twice the "rated" voltage?
Not good. Go back and pick another point. Within spec? Good. Now determine
the impedance. Z=(maxvoltage-quiescent voltage)/quiescent current. Alternately,
you can pick an impedance to suit available plate transformers. In this case,
if you go outside the safe boundaries, you must choose a new quiescent point.
This is where picking a loadline for the triode and the pentode differ. Maximum
power output and more-or-less minimum distortion for the pentode occurs where
the load line goes through the "knee" of the curve. This is illustrated above
for a load of 2.4k. Notice I have "exceeded" the tubes rating over a small
portion of the curve. You can do this, as the power dissipation over the
full conduction cycle is still within the tube rating. Make sure the idle
condition is within the ratings, however.
-
Having now chosen a tentative loadline, we need the following information
from it......
-
The required grid bias (you'll need to supply the grid with this value of
DC voltage).
-
The quiescent voltage (called Vq)
-
Voltage where the grid bias voltage is zero (called Va).
-
Voltage where the grid bias is double the quiescent value (called Ve). Note...
if the plate current reaches zero before you get to this bias, you've got
a bad operating point, go back to step 3 and try again.
-
Current at 0 volt grid bias (called Ia). If this current is above the maximum
rated tube current, go back to step 3 and try again. Hint: If its off the
scale, chances are the current is too high.
-
Current at half the quiescent bias voltage. (Called Ib.)
-
Quiescent Current.(Called Ic.)
-
Current at 1.5 times the quiescent bias voltage (Called Id).
-
Current at twice quiescent bias voltage. (Called Ie).
For our example, the data is as follows:
Va= 70V, Vq=300V, Ve=433V, Ia=180mA, Ib=130mA, Ic=83mA, Id=51.5mA, Ie=28mA.
In addition, 40V p-p are required from the driver stage, and a 2.4k plate
transformer is required.
Rectification Effects
In any device with even order distortion (not just second harmonic as sometimes
stated), the average current of a Class A stage will change depending on
the signal level. If the distortion is relatively low, the effect is relatively
unimportant, if the distortion is high, this effect becomes increasingly
important. (It is also more important for self bias than fixed bias, as the
bias voltage is a function of the average current).
This effect modifies all tube operating characteristics. The degree can be
seen by comparing the quiescent current (83 mA in our example) with the average
current as taken from the "extremes": that is, (Ia+Ie)/2. In our example
that value calculates to 104mA (note that since this is reasonably different,
we can expect relatively high distortion). The effect requires an iterative
plot of the load line on the tube characteristics as described in part 1
of this series. Note the quiescent dissipation is still 300*0.083, or in
this case 24.9 watts. The non-linearity shown here is getting dangerously
close to what can be ignored, but, as we will see, the distortion in this
example is too high anyway.
Power Output
Po = (Ve-Va)*(Ve-Va)/(8*loadimpedance).
In our example this is (433-70)*(433-70)/(8*2500)= 6.9 watts. This number
is an approximation in that it assumes low distortion.
Second Harmonic Distortion
HD2(%) = 75*(Ia + Ie - 2*Ic)/(Ia + Ib - Id - Ie)
In our example this is 14% (!)
Third Harmonic Distortion
HD3(%) = 50*(Ia - (2*Ib) + (2*Id) - Ie)/(Ia + Ib - Id - Ie)
In our example this is -1.1%
Notice the minus sign. This indicates that the harmonic content subtracts
from the fundamental (flattening it) when the fundamental is at its crest.
This *usually* happens on third harmonic distortion in tubes.
Fourth Harmonic Distortion
HD4(%) = 25*(Ia - (4*Ib) + (6*Ic) - (4*Id) + Ie)/(Ia + Ib - Id - Ie)
In our example this is -2.2%
It is also possible to get an indication of how distortion varies with power
output. In the example we just used, we picked 0, -10, -20, -30 and -40 volt
bias points. We could also use -10, -15, -20, -25 and -30 points to see what
happens at lower levels.
Applying the same formula to these points gives us 187 and 376 volts, and
130, 110.5, 83, 69.5 and 51.5 mA. This, in turn, calculates to 1.9 watts
and 9.7% second harmonic, -1.5% third harmonic, and -8.5% fourth harmonic.
This means the 2 watt level with this tube will also be pretty distorted!
Push Pull Operation (composite loadlines for pentodes)
We will discuss how to create a composite load line for a pentode. This is
"necessary" to establish the load line for a push pull amplifier, regardless
of whether it is going to be Class A or Class AB. We will continue to use
the same "invented" pentode. As we will discover, establishing a realistic
loadline for a pentode is slightly different than for a triode, due to the
shape of the characteristic curves.
Building a Composite Load Line
This is again an iterative process, perhaps moreso than the single ended
case as it's a bit more involved. Here's a step by step procedure to create
a set of "composite curves" and load line.
1. Establish your intended operating point from the single ended curves.
First let's consider an obvious Class A case, by choosing the same bias point
we used for the single ended case: 300 volts and 83 mA quiescent current
(-20 volt bias). Note: For Class AB, you may choose a lower idling current
point, which will allow a lower impedance loadline (and higher power output)
without exceeding maximum allowable power dissipation. For instance, choosing
a -25 or -30 volt quiescent point would allow you more "room" to increase
tube current. To stay within Class A operation, at least some current must
flow in each tube at all bias points, otherwise, you will be operating in
Class AB. In this article we will consider -20 volt bias point (requiring
a swing on each of the grids of 0 to -40 volts, -25 volts (which is still
technically class A, since there is some current still flowing at -50 volts
bias) and -30 volts, which is Class AB, since no current flows at -60 volts
bias. This is actually
an important distinction with pentodes. Since the "cutoff" characteristics
tend to be sloppier than a triode, most so-called Class AB amplifiers are
really Class A, as some small current is flowing even at the most negative
point. As we will see, truly Class AB has some pretty bad crossover
(notch) distortion.
2. Since the plate voltage increases on one plate and decreases on the other
plate, we must have a way of representing this. The usual method is to take
another set of the same tube curves, turn them around (so the maximum current
is "down" and highest plate voltage is to the "left", and position them so
that the quiescent voltages line up vertically, and the zero plate current
lines touch each other as shown below. I've shown the steps to do this on
the curves below: that is, copy the curves, turn one around, then merge the
curves as:
3. Now, for the chosen bias point, create a new line (labeled "composite"
curve) as follows (we are going to look at ONLY the
-20 volt bias lines, one on the "upper" part of the graph, one on
the "lower" part of the graph:
-
At the quiescent point (300V), subtract the currents (83-83=0 mA). Draw the
"dot" at 300V, 0 mA on the composite curves.
-
Step to the next convenient voltage, say 310/290 volts, and subtract the
currents. Plot this point.
-
Step to the next convenient voltage, say 320/280 volts, and subtract the
currents. Plot this point. Continue until you have the -20 volt bias point
established.
4. You have now established one "line" of the composite curves. This is the
line of varying the plate voltage symmetrically about the quiescent point
while maintaining a constant grid voltage. (classic plate resistance line).
5. Now consider another set of lines for your graph. This will be the
-25 volt line for the "upper" set and the -15 volt line from the lower set.
(We have put a 5 volt signal into the push pull stage). Again, for each plate
voltage, subtract the two currents (for instance, 310V -25V bias upper and
290 volt -15V lower) and plot the dot. Continue until you have the -25/-15V
line filled in. Note that if your quiescent grid voltage was, for instance,
-30 volts, the second line you would add would use the -35/-25V lines instead
of -25/-15V line.
6. Next do the same for the -30/-10, the -35/-5 and -40/0 volt lines.
Then do the same for the -15/-25, the -10/-30, the -5/-35 and the 0/-40 volt
lines. This completes the composite curves. The last 4 curves should be mirror
images of the previous 4 you filled in. Noticing this saves you some time.
7. The last thing to do is fill in the maximum power dissipation curve. There
are now going to be 2 of them, one for the one tube, one for the other. These
will be symmetrical about the quiescent point. It is usually necessary to
graph only half of the curve. The following is for the "upper" tube. Here's
how to do it:
-
Get the current at the quiescent point. (In our case that's -20 volts, 300V,
83 mA.) Each tube will be drawing this current. Now find the current allowable
via the power formula: I=P/E. In our case this is 25 watts at 300 volts or
83.3 mA. Since the "opposite" tube is pulling 83 mA, subtracting this from
our 83.3 ma gives 0.3 mA, which is the most (lets call it unbalanced) current
we can pull. Draw a dot at 300V, 0.3 mA.
-
Move to the next "convenient" grid line. This will correspond to moving "left"
by about 60 volts to 240 volts. At this point the tube we have 240 volts
on the upper tube, and the power formula states we could draw 25/240=104
mA. However, the "lower" tube has 360 volts on it, but is biased at -25 volts.
Looking this point up on the original single ended load line indicates 65
mA. Subtract the two to obtain 39 mA. Draw a point at 240 volts, 39 mA.
-
Repeat for a series of grid conditions just like we did for the triode case.
-
Now connect these with a nice smooth curve.
-
Rotate for the lower tubes power condition: it's a mirror image remember.
You should now have a graph that looks like this...
Push Pull Load Line
The same rules we used in the single ended case apply, with one exception:
The impedance you plot is the impedance AS SEEN BY A SINGLE TUBE. Thus it
is 1/4 the plate to plate load impedance. Lets use a 6000 ohm plate to plate
load. In this case, each tube sees 1500 ohm load, and one "point" on the
loadline is the 300 volt "0" mA quiescent value. Another convenient point
is at "0" volts (namely, 300 volts drop across the 1500 ohm load). By ohms
law, this is i = e/r = 300/1500 = 200 mA. As in the SE case, we need to obtain
the same 5 currents and 2 voltages to give us the power output and distortion
prediction.
Remember the formulas we used:
Po=(Ve-Va)*(Ve-Va)/(8*RL)
HD2=75*(Ia+Ie-(2*Ic))/(Ia+Ib-Id-Ie)
HD3=50*(Ia-(2*Ib)+(2*Id)-Ie)/(Ia+Ib-Id-Ie)
HD4=25*(Ia-(4*Ib)+(6*Ic)-(4*Id)+Ie)/(Ia+Ib-Id-Ie)
These work, with the RL value equal to a single tubes load (1500 ohms in
our example).
The values from the graph are: Va=71V, Ve=529V, Ia=151, Ib=77, Ic=0, Id=-77,
Ie=-151.
| Power Out |
HD2(%) |
HD3(%) |
HD4(%) |
| 17.5 watts |
-0- |
0.7 |
-0- |
Notice in the push pull configuration, even order distortion "cancels". Also,
of more importance is the fact that the ODD order is reduced over the single
ended case, even though the power output is more than double the SE case.
Even more important is the significance of the picked load. Again, we picked
a loadline that goes through the "knee" of the composite curves. We will
show below, that as the bias conditions are altered, the "best fit" impedance
changes also, which is quite a change from the triode case.
This is one case where the operation of these two device types is quite
different.
The Effect of changing the bias on Pentode Composite Curves
Let's choose a -25 volt bias on the tubes, which will drop the idle current
to 60 mA. As I mentioned above, technically, this is still Class A operation.
The curves look like this:
One important item to note is that now, an appropriate load line is 5.2k
instead of 6k. (Substantially lower load impedance produces lower power and
higher distortion, as does substantially higher load impedance.)
For this condition, The seven values picked from the curve are 74V, 526V,
174, 83, 0, -83 and -174 mA.
| Power Out |
HD2(%) |
HD3(%) |
HD4(%) |
| 19.6 watts |
-0- |
1.6 |
-0- |
Notice the available power output has increased, but so has the distortion.
This is even more obvious if we move the class of operation into true Class
AB:
Now, the appropriate loadline has decreased to 5k, but the power output has
reached 20 watts.
We can pick 0, -15, -30, -45 and -60 volt points (which gives us full 20
watts output) or choose intermediate points. This is summarized in the following
table:
| Power Out |
HD2(%) |
HD3(%) |
HD4(%) |
| 20 watts |
-0- |
2.5 |
-0- |
| 8.9 watts |
-0- |
5 |
-0- |
| 1.5 watts |
-0- |
3.4 |
-0- |
Now you can see the effect of the "compressed" curves around zero bias. The
distortion is actually greater at low levels than at maximum output. This
is the effect of crossover or notch distortion.
-Steve
|